Monitor up to 24 single phase circuit or 8 separate 3-phase circuits. Modbus rtu over rs485 communication max voltage : 80 350 vac l-n 600 vac l-l frequency : 50 or 60 hz. Display kwh real time kw volts amps power factor apparent power kva reactive power kvar reactive energy kvarh frequency. Auxiliary power: ac 120 or 240v 10% 2 lines 16 characters lcd display for easy set-up and programing. Depending on your electrical system you will need: 1 ct for each 120v 1 phase 2 wire 1 hot wire 1 neutral circuit 1 ct for each 240v 1 phase 2 wire 2 hot wires circuit 2 cts for each 120 240v 1 phase 3 wire 2 hot wire 1 neutral circuit 2 cts for each 208v or 480v 3 phase 3 wire 3 hot wire no neutral circuit 3 cts for each 120 208v or 277 480v 3 phase 4 wire 3 hot wire 1 neutral circuit. Non-volatile memory the stored data is maintained through power outages. No conversion factor or multiplier required compatible with touch panel like dae acs35 see dae website for details for remote display. Current transformers cts are not direction sensitive. It does not matter if the contractors install the cts with wrong direction of current. Dae meters can detect it and compensate it. Dae’s cts are exactly the same and exchangeable among all the meters including polaris 1000 1500 2000 2500 3000 and smb 350 multi-circuit multi-function meters. Current sensors cts accuracy will not be affected when the cts are mounted up to 2000 feet away from the meter. Applications: multi-apartments commercial pro...
Brand: DAE